6.0Mpa Hfc227ea Piston Flow Clean Agent Fire Suppression System Fire Fighting Equipment

Brand Name : Air Giant

Model Number : QMQ5.6/90W, QMQ5.6/120W, QMQ5.6/150W, QMQ5.6/180W, QMQ4.2/245W

Certification : CAL,CMA,CNAS,ILAC-MRA,CCC

Place of Origin : China

MOQ : 1 set

Price : negotiation

Payment Terms : L/C , D/P, T/T, Western Union, Paypal, Credit card

Supply Ability : 3000 sets per month

Delivery Time : 10-15 working days

Packaging Details : Plywood outer box with bubble bag or paper

Cylinder Volume : 90Ltr, 120Ltr, 150Ltr, 180Ltr, 245Ltr

Filling Pressure : 5.6 MPa, 4.2 MPa

Filling Density : ≤1250kg/m³

Pressure Of Adding Pressure : 13.5MPa

Discharge Time : ≤10s

Driving Device Pressure : 6.0MPa(20℃)

Power : DC24V/1.6A

Contact Now

6.0Mpa Hfc227ea Piston Flow Fire Fighting Equipment without residue

Fm200(hfc-227ea) is a kind of clean gas extinguishing agent with chemical extinguishing and physical extinguishing.It is colorless, tasteless, low toxicity, non-conductive, does not pollute the protected object.

The piston flow type heptafluoropropane fire suppression system, which is produced by our company, absorb the advanced technology of gas fire extinguishing research at home and abroad. It is high strength safety factor, strong work reliability, convenient operating and maintenance. At the same time, the system has automatic and manual driving mode. It relies on external driving force to push the agent farther in the effective fire-fighting time.

Parameters

No. Name Specification
1 Device Model QMQ5.6/90W, QMQ5.6/120W, QMQ5.6/150W, QMQ5.6/180W, QMQ4.2/245W
2 Cylinder Volume 90Ltr, 120Ltr, 150Ltr, 180Ltr, 245Ltr
3 Filling Capacity of Gas 112.5kg, 150kg, 187.5kg, 225kg, 306.25kg
4 Max Working Pressure 8MPa, 5.3MPa
5 Max protected area Single zone: 800m2
6 Max protected volume Single zone: 3600m3
7 Spraying Time ≤10s
8 Agent Filling Density ≤1250kg/m3
9 Power DC24V/1A
10 Pressure of Adding Pressure Cylinder 13.5MPa
11 Pressure of Driving Device 6.0MPa(20℃)
12 Condition of Reserving Room for Container Temperature: 0~50℃

System Composition

This system mainly consists of agent storage cylinder, container valve, driving cylinder group, adding pressure cylinder group, distributing valve, liquid flow check valve, gas flow check valve, safety valve, pressure switch, frame, nozzle, high pressure hose, pressure-relief device, level gauge, relief valve, pipe system, which can constitute the unit independent system. Combined distribution system and other forms can implement fire protection for single and multiple zones.

Pipe fittings are those conduits to connect extinguishing device and guide agent into protective zone, like high pressure galvanized steel pipe and flange and elbow.

Electrical accessories are those things which are used to detect and monitor whole protective area and control whole system, also warn people to evacuate and prevent from fire expansion.

These integrated three parts will be efficient to detect and supervise and alarm and extinguish fire automatically.

6.0Mpa Hfc227ea Piston Flow Clean Agent Fire Suppression System Fire Fighting Equipment

Application

  1. • Computer room, communication room, power distribution room, library, archives,

    Museum, etc.

    • Be used for electrical fire, liquid fire, solid fire, gas fire which can be cut off the gas

    source before extinguishing occur, etc.

Packages

We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.


Product Tags:

6.0Mpa Hfc227ea Fire Fighting Equipment

      

Hfc227ea Piston Flow Clean Agent Fire Suppression System

      

Hfc227ea Piston Flow Fire Fighting Equipment

      
Quality 6.0Mpa Hfc227ea Piston Flow Clean Agent Fire Suppression System Fire Fighting Equipment for sale

6.0Mpa Hfc227ea Piston Flow Clean Agent Fire Suppression System Fire Fighting Equipment Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Guangdong Air Giant Fire Equipment Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)